STORAGE COMPOUND
  Characteristics Of Circuit
Lighting protection circuits, avoid high voltage penetration and keep stable circuit voltage.
Termanal resistors configured on the circuit board.
Every circuit with an isolating switch.
In operation, switch in off position to avoid power failuare false report.
Short circuit indicating light at every 5L joint-postion recognizes short circuit from motion perception.


Storage Function
2-phase signal confirmation.
Help to elimantae false fo disturbance.
Auto reset the first reported fire alarm signal and re-perform scanning and detection before sending alarm message.


Main Circuit Board
External indicating lights and zone bells relay-controlled, voltage output stable.
All fuse wires with protectors and power failure indicating lights.
Stable voltage IC-control battery charge, enable extend battery time.
 
Design
External lines configured into PCB through wiring ducts to avoid short circuit caused by external line's contact with internal lines.
Easy to maintain- Int the evernt of power failure, unplug power cord to replace defected circuit.
A special designed IC-control supervisory LED, on the back of the panel, provides monitoring the machine operation. And it is constantly flashing when monitoring.


 
Model LA-2000
Input Voltage
110V AC or 220V AC (50Hz/60Hz)
Battery
DC-24V
Circuit Voltage
DC-24V (DC 18V ~ DC 30 V)
Terminal Resistor
10KO, 1/4 TO 1/2W
External Resistor
Below 50 KO(Short circuit)
Detector
SMOKE DETECTOR, RATE OF RISE HEAT DETECTOR, FIXED-TEMPERATURE DETECTOR
Main Bell
24VDC, 90dB
Alarm Bell
Within 24V 30mA up to 1.3 times circuits
Dry Auxiliary Alarm
240VAC/5A 120VAC/10A 24VDC/10A
Handset
Wtih handset
Cabinets
1.6mm Steel plate; Ivory white lacquer
Spare
Terminal resistance, Fuses, Schematic diagrams